Conventional Zone Monitor Module MI/DCZRM

Availability: available
Brand: Honeywell Morley-IAS
Please sign in to buy

This product cannot be added to the
cart because you are not logged in.

Add to wish list Add to comparison list

Conventional Zone Monitor Module

  • Connection of a zone of non-addressable detectors to an analogue addressable fire system
  • Built in isolation allowing system installation in stages without loss of protection
  • Rotary decade address switches
  • Monitors open circuit and short circuit faults
  • TRI-Color Status LED
  • Zone powered from addressable loop wiring or external 24V PSU
  • Remote reset of non-addressable zone
  • Compatible with most non-addressable detectors, IS non-addresable detectors
  • Monitoring of external power supply
  • External fault input
  • Specifications: EN54-17, EN54-18
  • LPCB approved
  • DIN rail mountable, consistent with all other modules
  • Support for an extended power supply range as low as 18Vdc 60mA with an External PSU

 

Operating voltage 18 ... 28.5 V DC
Dimension H: 93 mm W: 83 mm D: 23 mm
Weight 110 g
Temperature range -20°C ... 60°C
Quiescent current 375 uA @ 24 V DC
Relative humidity 5% ... 95% (non-condensing)
Max Standby current 288 uA (conventional Zone connected to external supply
End of line resistor 3.9 K
Weight:
0.183 кг